#SR2 Heat Exchanger Plate
Explore tagged Tumblr posts
Text
Plate heat exchanger internal leaking
The advantage of the plate heat exchanger is that under the same pressure loss, the heat transfer coefficient is 3-5 times higher than that of the column heat exchanger, and the area is one-third of the tube heat exchanger. However, if a leak occurs during use, this will affect the efficiency of the equipment. How should we solve this problem?
1. Make a mark on the leakage area, and then disassemble the heat exchanger one by one to check and solve, reassemble or replace the gaskets and plates. 2. In the no-pressure state, re-clamp the device according to the clamping size provided by the manufacturer. The dimensions should be uniform and the deviation of the pressing size should not be greater than ยฑ 0.2N (mm) (N is the total number of plates). The parallelism between the plates should be kept within 2mm. 3. When reassembling the disassembled plate, clean the surface to prevent dirt from adhering to the sealing surface of the gasket. 4. Disassemble the open plate heat exchanger and repair or replace the deformed part of the plate. When spare parts are not available, the deformed parts can be temporarily removed and reassembled. We have 10 years experience in designing in this field and solve various problems for you. Industry heat exchanger plate application of Automotive industry, Food industry, Pharmaceutical industry, Process Technology, Compressor systems, etc. Our engineers can help you design and select the model and configuration that is suitable for your application. Welcome to browse our website: http://www.jinfanmoju.com/.
#plate heat exchanger#plate heat exchanger maintenance#plate heat exchanger leaking#FP10 Heat Exchanger Plate#SR2 Heat Exchanger Plate
0 notes